kVA to amps calculator

Useful when sizing a generator or transformer, or checking that cables and breakers can carry the full-load current.

Loading the tool…

Processing and privacy: The result is calculated inside your browser and your data is not sent to any server.

How to use it

  1. Enter phases, apparent power and voltage.
  2. The result appears straight away and updates as you edit.
  3. Copy the result, or copy a link that keeps the same values to share it.

How it is calculated

Single-phase: I = kVA × 1000 ÷ V. Three-phase: I = kVA × 1000 ÷ (√3 × V) with V the line voltage.

Example

Inputs: Phases = Three-phase, Apparent power = 100 kVA, Voltage = 400 V. Result: Full-load current: 144.34 A; Real power at PF 0.8: 80 kW.

Limits and caveats

  • Assumes a load balanced across the three phases.
  • Real power is shown at a power factor of 0.8, the usual generator rating basis; your load may differ.

Questions about this tool

Why are generators rated in kVA?

Winding heat depends on total current whatever the power factor. Real power in kW equals kVA × PF.

How many amps does a 1000 kVA transformer give at 11 kV?

About 52.5 A on the 11 kV side. On the 400 V side it is about 1443 A.

Which voltage do I enter for three-phase?

The line-to-line voltage, such as 400 or 415 V, not the phase-to-neutral voltage.