Solar battery size calculator

Find the storage that runs your loads at night or on cloudy days without draining the batteries too deep.

Loading the tool…

Processing and privacy: The result is calculated inside your browser and your data is not sent to any server.

How to use it

  1. Enter daily load, days of autonomy, system voltage, allowed depth of discharge, inverter efficiency and capacity of one battery.
  2. The result appears straight away and updates as you edit.
  3. Copy the result, or copy a link that keeps the same values to share it.

How it is calculated

Capacity (Ah) = daily load (Wh) × backup days ÷ (system voltage × depth of discharge × inverter efficiency). Series = system V ÷ battery V; parallel = round up (capacity ÷ battery Ah).

Example

Inputs: Daily load = 3,000 Wh, Days of autonomy = 1, System voltage = 24 V, Allowed depth of discharge = 80 %, Inverter efficiency = 90 %. Result: Capacity needed: 173.6 Ah; Nominal bank energy: 4.17 kWh; Total batteries: 4.

Limits and caveats

  • 80% depth of discharge suits most lithium batteries; lead-acid is usually kept to 50%.
  • Heat losses and battery ageing are not included.

Questions about this tool

How many batteries for 3,000 Wh a day?

On 24 V with 80% discharge and a 90% inverter you need about 174 Ah, which is four 12 V 100 Ah batteries.

What is the difference between series and parallel?

Series raises voltage at the same capacity; parallel raises capacity at the same voltage.

Why not drain the battery fully?

Repeated deep discharge shortens battery life, especially for lead-acid.